Shielded  PVC - Data - Cable - LiYCY-CY - 224
 
               
 
 
       
           
           
with filler if necessary                
Applications: 26AWG (0,14 mm²) Stranding: VDE 295, class 5  (18 x 0,1 mm)
Sensor Technology Part Numbers cond. O.D. inches O.D. mm Part Numbers cond. O.D. inches O.D. mm
Computers 224-0001-002 2 0.24 6.1 224-0001-005 5 0.30 7.7
Measurement devices 224-0001-003 3 0.25 6.4 224-0001-007 7 0.33 8.3
Control devices 224-0001-004 4 0.28 7.1        
Whenever electrical interference 24AWG (0,25 mm²) Stranding: VDE 295, class 5  (14 x 0,15 mm)
distorts signal transmission. Part Numbers cond. O.D. inches O.D. mm Part Numbers cond. O.D. inches O.D. mm
Specifications: 224-0002-002 2 0.25 6.4 224-0002-005 5 0.34 8.5
According to VDE  224-0002-003 3 0.28 7.2 224-0002-007 7 0.36 9.2
0281, 0812 224-0002-004 4 0.31 7.8        
                 
Construction:                
Conductors:                
bare copper strands acc. to                
VDE 0295, class 5, with PVC                
insulation                
Color code:                
acc. to DIN 47100                
see color code table                
Stranding:                
each PVC insulated wire with                
braided shield and inner PVC                
jacket, all twisted in layers with                
common braided shield and foil                
Jacket:                
PVC gray, with common braided                
shield, self-extinguishing and                 
flame retardant.                
Technical Data:                
Rated voltage:                
300 Volt                
Test voltage:                
1,200 Volt                
Bending radius:                
fixed: 5 x diameter                
flexible app.: 15 x diameter                
Temperature range:                
fixed:  -22°F to 176°F                 
flex.:    23°F to 158°F