| Power ratings | ||||
| This chart shows the loadability of | Nominal cross | Group 1 | Group 2 | |
| flexible cables with a rated voltage up | section | Current rating | Current rating | |
| to 1000 Volt. | ||||
| 0.14 mm² | 26AWG | 1.5 Ampere | 2 Ampere | |
| 0.25 mm² | 24AWG | 3 Ampere | 4 Ampere | |
| Group 1 | 0.34 mm² | 22AWG | 4 Ampere | 6 Ampere |
| Single core cables with stranded | ||||
| wires | 0.50 mm² | 20AWG | 7 Ampere | 9 Ampere |
| 0.75 mm² | 18AWG | 9 Ampere | 12 Ampere | |
| Group 2 | ||||
| Multi core cables with stranded | 1.00 mm² | 17AWG | 11 Ampere | 15 Ampere |
| wires | ||||
| 1.50 mm² | 16AWG | 15 Ampere | 18 Ampere | |
| All at ambient temperature of | 2.50 mm² | 14AWG | 20 Ampere | 26 Ampere |
| 30°C (86°F) | ||||
| 4.00 mm² | 12AWG | 25 Ampere | 34 Ampere | |
| Extract from VDE 0298 part 4, | 6.00 mm² | 10AWG | 33 Ampere | 44 Ampere |
| VDE 100 part 523 as well | ||||
| as VDE 0891 | 10.00 mm² | 8AWG | 45 Ampere | 61 Ampere |
| 16.00 mm² | 6AWG | 61 Ampere | 82 Ampere | |
| 25.00 mm² | 4AWG | 83 Ampere | 108 Ampere | |
| 35.00 mm² | 2AWG | 103 Ampere | 135 Ampere | |
| 50.00 mm² | 1AWG | 132 Ampere | 168 Ampere | |
| 70.0 mm² | 2/0AWG | 165 Ampere | 207 Ampere | |